Details
Description
When the firmware receives an acyclic service request from network and processes a Check Indication service in parallel, either the acyclic service or the Check Indication service may be corrupted. The problem can most likely be seen when a submodule is plugged at the same time a Read/Write record access occurs. Affected services from this behavior are:
- Check Indication Service
- AR Check Service
- Parameter SpeedUp Service
- Read Record Service
- Write Record Service
- Read I&M Service
- Write I&M Service
- Get Asset Service
Attachments
Issue Links
- relates to
-
PSPNDIF-192 Check service indication may block RPC services
- Closed
-
PSPNSV5-438 Unexpected pnio status when reading record immediately after plugging submodule
- Closed
-
PSPNSV4-1451 Check Indication service and parallel running acyclic services may corrupt each other in LOM usecase
- Closed
- requested
-
PSPNDIF-234 Check Indication service and parallel running acyclic services may corrupt each other
- Closed
-
PSPNSV5-528 Upgrade Profinet Device Interface to V1.5.0.2
- Closed
-
PSPNSV5-529 Upgrade Profinet Device Interface to V1.4.0.3
- Closed