Flash based targets: NameOfStation set via DCP is stored directly in the database file

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V3.5.54.0
    • Fix Version/s: V3.10.0.3, V3.10.1.0, V3.11.0.0
    • Component/s: None
    • Labels:
      None
    • Sprint:
      PI Sprint 2016 KW 20/21, PI Sprint 2016 KW 22/23
    • Account:
      SPC Profinet Slave (SPCPROFINE)

      Description

      If a NameOfStation is set via DCP it needs to be stored by a PROFINET IO Device.
      In case of loadable firmware with database configuration this needs to be done by the PROFINET IO Device firmware.

      Expected behavior: Both configuration files "config.nxd" and "nwid.nxd" are not changed when NameOfStation is set via DCP.
      Observed behavior: "nwid.nxd" is changed by the firmware when NameOfStation is set via DCP.

      The observed behavior is bad in case the Hilscher cifX Toolkit is used to configure the firmware. After a power cycle it will detect that "nwid.nxd" is changed and thus will download its copy of the file. As consequence the NameOfStation set via DCP is gone.