Uploaded image for project: 'PROFINET IO-Device V5'
  1. PROFINET IO-Device V5
  2. PSPNSV5-806

Feature InputValidOnBackupAR can not be used in combination with DynamicReconfiguration

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V5.2.0.0, V5.3.0.0, V5.4.0.0, V5.5.0.0, V5.6.0.0, V5.7.0.0
    • Fix Version/s: V5.8.0.0, V5.8.1.0 (trunk)
    • Labels:
      None
    • Account:
      SPC Profinet Slave V5 operational (SPCPROFINE)

      Description

      As of current GSDML and Profinet Device stack implementation, the firmwares accept the InputValidOnBackupAR operation mode for SR-ARs. However, considering the usecase Dynamic Reconfiguration (DR), this is not valid because with DR we need to supply the AR using the old configuration with valid IO Data. This is however not possible with the current data model and DPM interface of the firmware.

      For now, we will keep the implementation as it is for compatibility reasons but need to document this restriction accordingly.

        Attachments

          Issue Links

            Expenses

              Activity

                Status Description

                  People

                  • Reporter:
                    AMesser Andreas Messer
                  • Votes:
                    0 Vote for this issue
                    Watchers:
                    0 Start watching this issue

                    Dates

                    • Created:
                      Updated:
                      Resolved: