Description
When aborting an AR, the communicating bit might be cleared before the AR has been fully shutdown. In that situation, reading immediately the DPM input area might return non-zero data or GOOD IOPS although the Com bit is already cleared.
It is expected that when handshaking the DPM Input area immediately after the communicating bit is cleared also clears the DPM input area.
Attachments
Issue Links
- blocks
-
PSPNSV5-58 Upgrade Profinet Device Interface to V1.0.0.1
- Closed
-
PSPNCORE-285 Notify application when AR resource fully released
- Closed
-
PSPNDIF-58 [GCI] Handle communicating bit depending on previous state
- Closed
-
PSPNSV5-53 Upgrade Profinet Core to V1.8.0.1
- Closed
- relates to
-
PSPNSV4-1084 Communicating Bit cleared to early
- Closed