Details
-
Type: Bug
-
Status: Closed
-
Priority: Minor
-
Resolution: Fixed
-
Affects Version/s: V5.3.0.0
-
Fix Version/s: V5.3.0.8
-
Labels:
-
Account:SPC Profinet Slave (SPCPROFINE)
Description
In case of Shared Device (multiple ARs at the same time) it may happen that Write Requests from IO Controller are negatively responded on the network although the request was never forwarded to application.
Occurrence depends on application timing and was only observed in a single customer application.
Attachments
Issue Links
- is blocked by
-
PSPNSV5-327 Upgrade Profinet Core to V1.11.0.9
- Closed
- relates to
-
PSPNCORE-474 Write.req might be unexpectedly rejected during plug sequence
- Closed
-
PSPNSV5-510 Sometimes Plug Alarm not sent in case of Shared Device
- Closed
- requested by
-
PSPNCORE-479 Write Record request might be rejected during plug sequence
- Closed