Details
-
Type:
Bug
-
Status: Closed
-
Priority:
Minor
-
Resolution: Fixed
-
Affects Version/s: V3.13.0.3, V3.14.0.0
-
Component/s: Firmware
-
Labels:
-
Account:SPC Profinet Slave (SPCPROFINE)
Description
According to specification APDU_Status.ProblemIndicator is set when at least one diagnosis with severity "faulty" exists.
The device sets APDU_Status.ProblemIndicator depending on the submodule state, where only submodules in states "PNIO_SUBSTATE_SUBSTITUTE_SUBMODULE" and "PNIO_SUBSTATE_PROPER_SUBMODULE" are relevant.
In case of submodule configuration adaption, if the application uses the "Obsolte" state "PNIO_SUBSTATE_CORRECT_SUBMODULE" in Check ind response packet the device ignores these submodules while updating the APDU_Status.ProblemIndicator.
Attachments
Issue Links
- relates to
-
PSPNS-2817 In some cases on connection abort not all unused check indications are generated
-
- Closed
-