Description
Acoording to PNIO Diagnosis Guidline, the device shall indicate the disappearance off all "Remote mismatch" releated diagnosis when "No Peer detected" is reported. This is currently not done.
If a specific ExtChannelErrorType (e.g. ExtChannelErrorType y) is below another ExtChannelErrorType (in this sample ExtChannelErrorType x), a coming diagnosis with ExtChannelErrorType x will purge the underlying ExtChannelErrorType. This is not done automatically; the application has therefore to add ExtChanneleErrorType x first, and then to remove ExtChannelErrorType y.
Attachments
Issue Links
- relates to
-
PSPNS-2737 Disappearance of "No Peer detected" diagnosis not reported when an other "Remote mismatch" releated diagnosis exists
- Closed
-
PSPNS-2739 Sometimes RT Class 3 mismatch not reported as expected
- Closed