Details
-
Type: Bug
-
Status: Closed
-
Priority: Minor
-
Resolution: Fixed
-
Affects Version/s: V3.7.0.0
-
Fix Version/s: V3.12.0.11, V3.12.2.0, V3.13.0.0
-
Component/s: None
-
Labels:
-
Sprint:PI Sprint 2018 KW 11/12
-
Account:SPC Profinet Slave (SPCPROFINE)
Description
When a connection is established in legacy startup mode, an unexpected CMI timeout might be observed. The problem can only be observed with a slow application delaying the application ready by more than 60 seconds.
The CMI monitoring is not stopped and the CPM monitoring is not started when RPC Write or RPC ParamEnd is received as required by Profinet Specification V2.2.
Attachments
Issue Links
- relates to
-
PSPNSV4-821 Wrong CMI/CPM connection monitoring in for legacy startup
- Closed
-
PSPNS-2775 SPIRTA tests randomly failue due to Advanced Startup CPM monitoring
- Closed