Details
-
Type: Bug
-
Status: Closed
-
Priority: Minor
-
Resolution: Fixed
-
Affects Version/s: V1.11.0.10, V1.12.0.3, V1.13.0.1, V1.14.0.0
-
Fix Version/s: V1.13.0.11, V1.14.0.10, V1.15.0.0
-
Component/s: Controller, Device
-
Labels:None
-
Account:SPC Profinet Core (SPCPROFINET)
Description
When the length of the red period is calculated only the first port is considered. The second port is not taken into account. This leads to an invalid cyclic scheduler configuration when the Profinet Controller is reached via the second port of the device.
Attachments
Issue Links
- blocks
-
PSPNSV4-1488 Profinet IRT Communication not working for large output data
- Closed
-
PSPNSV4-1491 IRT Communication failure when using port 2
- Closed
-
PSPNSV5-571 IRT Communication failure when using port 2
- Closed
-
PSPNSV4-1490 Upgrade Profinet Core to V1.13.0.11
- Closed
-
PSPNSV5-552 Upgrade Profinet Core to V1.15.0.0
- Closed
-
PSPNSV5-572 Upgrade Profinet Core to V1.14.0.10
- Closed
-
PSPNSV5-573 Upgrade Profinet Core to V1.13.0.11
- Closed
- relates to
-
PSPNCORE-495 Unstable IRT operation of all eCos based firmwares
- Closed
-
PSPNCORE-705 IRT communication with large output data not possible
- Closed