Details
-
Type: Bug
-
Status: Closed
-
Priority: Minor
-
Resolution: Fixed
-
Affects Version/s: V1.11.0.10, V1.12.0.3, V1.13.0.1, V1.14.0.0
-
Fix Version/s: V1.14.0.10, V1.15.0.0
-
Component/s: Controller, Device
-
Labels:None
-
Account:SPC Profinet Core (SPCPROFINET)
Description
When the Profinet Device has more than 150 byte output data or the frame size of output IOCR exceeds 170 byte, IRT communication might be not established or unstable. The problem is caused by wrong internal timing which does not consider the frame reception time. The issue might also affect the Profinet Controller when large Input IOCRs are used in conjunction with only a few devices.
Unfortunately a similar issue was already addressed in PSPNCORE-495 but not fully fixed.
The fix for this issue may have an impact on T_IO_OutputMin of applications.
Attachments
Issue Links
- blocks
-
PSPNSV4-1488 Profinet IRT Communication not working for large output data
- Closed
-
PSPNSV5-574 Profinet IRT Communication not working for large output data
- Closed
-
PSPNSV4-1471 Upgrade Profinet Core to V1.15.0.0
- Closed
-
PSPNSV4-1489 Upgrade Profinet Core to V1.14.0.10
- Closed
-
PSPNSV5-552 Upgrade Profinet Core to V1.15.0.0
- Closed
-
PSPNSV5-572 Upgrade Profinet Core to V1.14.0.10
- Closed
- relates to
-
PSPNCORE-706 Invalid RTC phase length calculation
- Closed
-
PSPNCORE-495 Unstable IRT operation of all eCos based firmwares
- Closed