Uploaded image for project: 'EtherNet/IP Firmware V3'
  1. EtherNet/IP Firmware V3
  2. PSEISV3-468

Get_Attribute_All response of TCP/IP Interface object holds invalid data for Safety Network Number (SNN) attribute in case the SNN is not supported

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V3.4.3.0
    • Fix Version/s: V3.4.4.0, V3.5.0.0
    • Component/s: None
    • Labels:
      None
    • Account:
      SPC EthernetIp Slave (SPCETHERNE)

      Description

      Get_Attribute_All response of TCP/IP Interface object holds invalid data for Safety Network Number (SNN) attribute in case the SNN is not supported.

      The SNN part inside the response should be all zeros. Instead the stack delivers all FFs.

       

        Attachments

        1. pastedImage.png
          13 kB
          Kai Michel
        2. pastedImage.png
          13 kB
          Kai Michel

          Issue Links

            Expenses

              Activity

                Status Description

                  People

                  • Reporter:
                    KMichel Kai Michel
                  • Votes:
                    0 Vote for this issue
                    Watchers:
                    0 Start watching this issue

                    Dates

                    • Created:
                      Updated:
                      Resolved: