Get_Attribute_All response of TCP/IP Interface object holds invalid data for Safety Network Number (SNN) attribute in case the SNN is not supported

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V3.4.3.0
    • Fix Version/s: V3.4.4.0, V3.5.0.0
    • Component/s: None
    • Labels:
      None
    • Account:
      SPC EthernetIp Slave (SPCETHERNE)

      Description

      Get_Attribute_All response of TCP/IP Interface object holds invalid data for Safety Network Number (SNN) attribute in case the SNN is not supported.

      The SNN part inside the response should be all zeros. Instead the stack delivers all FFs.

       