APDU Status change not reported in all cases of SR-AR scenarios

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V5.4.1.0, V5.5.0.0, V5.6.0.0, V5.7.0.0
    • Labels:
      None

      Description

      When the Profinet IO Device stack is communicating in an SR-AR configuration with both SR AR established, the following sequence will not report an APDU status indication

      1. First SR-AR is Primary, second SR-AR is Backup
      2. The first SR-AR aborts and the second SR-AR takes over
      3. The second SR-AR is aborted as well
      4. The seond SR-AR is restablished
      5. The second SR-AR becomes primary

      It is expected that the stack generated an APDU Status indication after (5).