Uploaded image for project: 'PROFINET IO-Device V4'
  1. PROFINET IO-Device V4
  2. PSPNSV4-659

ResetToFactory with suboption "Reset communication parameter" shall no longer delete writable SNMP variables

    Details

    • Type: Change
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V4.3.0.0
    • Fix Version/s: V4.3.1.0, V4.4.0.0
    • Labels:
      None
    • Sprint:
      PI Sprint 2017 KW 36-37
    • Account:
      SPC Profinet Slave (SPCPROFINE)

      Description

      Due to a clarification in Profinet specification it is now recommended NOT to delete writable SNMP variables if a ResetToFactory with suboption "Reset communication parameter" is received.

      Earlier specifications allowed deleting SNMP.

      New versions of PI certification tools now complain ("Pass with hint") about the implemented behavior although it is not really a problem.

        Attachments

          Issue Links

            Expenses

              Activity

                Status Description

                  People

                  • Reporter:
                    BMeyer Benjamin Meyer
                  • Votes:
                    0 Vote for this issue
                    Watchers:
                    0 Start watching this issue

                    Dates

                    • Created:
                      Updated: