Uploaded image for project: 'PROFINET IO-Device V4'
  1. PROFINET IO-Device V4
  2. PSPNSV4-483

APDUStatus.ProblemIndicator is unexpectedly set for Diagnosis of severity Maintenance Demanded/Required

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V4.2.0.0
    • Fix Version/s: V4.2.0.17, V4.2.1.0
    • Labels:
      None
    • Sprint:
      PI Sprint 2016 KW 47/48
    • Account:
      SPC Profinet Slave (SPCPROFINE)

      Description

      According to Profinet specification the APDUStatus.ProblemIndicator shall only be set if a Diagnosis of severity "Fault" exists.
      Diagnosis of severity "Maintenance Required" and "Maintenance Demanded" shall not set the APDUStatus.ProblemIndicator.

        Attachments

          Issue Links

            Expenses

              Activity

                Status Description

                  People

                  • Reporter:
                    BMeyer Benjamin Meyer
                  • Votes:
                    0 Vote for this issue
                    Watchers:
                    0 Start watching this issue

                    Dates

                    • Created:
                      Updated:
                      Resolved: