Details
-
Type:
Bug
-
Status: Closed
-
Priority:
Major
-
Resolution: Fixed
-
Affects Version/s: V4.9.0.0
-
Fix Version/s: V4.9.0.2, V4.9.1.0 (trunk)
-
Labels:None
-
Account:SPC Profinet Slave V4 operational (SPC-PSPNSV4-OPERATIONAL)
Description
Precondition:
Firmware is configured and visible via DCP on the network, has an IP address assigned and application has an active TCP socket. No cyclic Profinet communication is established.
Error trigger:
The IP address is changed via Profinet DCP protocol.
Error consequence:
The device is no longer reachable/visible via IP. ARP frames are not responded, SNMP is not working, Profinet RPC based services are no longer working.
A powercycle is required to recover the device.
Affected versions:
PNS V4.9.0.0 and V4.9.0.1 are affected. Older branches, e.g. V4.8.0.x, are not affected.