Uploaded image for project: 'PROFINET IO-Device'
  1. PROFINET IO-Device
  2. PSPNS-2927

add possibility to parameterize the link status handling software timer for fiber optic mode

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: None
    • Fix Version/s: V3.14.0.8, V3.14.1.0
    • Component/s: Stack
    • Labels:
      None

      Description

      For netX51 in fiber optic mode, a software timer is used to handle link interrupts (due to a known issue with instable link detection). Currently this timer is using a hard coded 300ms timeout.

      For specific hardware layouts, this timer needs to use a longer timeout value. In this ticket, a possibility to configure this timer shall be given. Default timeout shall be 300ms.

      Configuration shall be done by adding a Profinet-specific, new parameter to  RX_EDD_PARAMETERS_T structure via config.c. If the parameter is not provided, 300ms shall be used. If parameter is provided, the value shall be used instead.

        Attachments

          Issue Links

            Expenses

              Activity

                Status Description

                  People

                  • Reporter:
                    BMeyer Benjamin Meyer
                  • Votes:
                    0 Vote for this issue
                    Watchers:
                    0 Start watching this issue

                    Dates

                    • Created:
                      Updated:
                      Resolved: