Different values reported for Type Of Station by DCP protocol

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V3.13.0.0
    • Fix Version/s: V3.13.0.3, V3.13.2.0, V3.14.0.0
    • Component/s: None
    • Labels:
      None
    • Account:
      SPC Profinet Slave (SPCPROFINE)

      Description

      As of Protocol Version V3.13 the use of abTypeOfStation field in Set Configuration service has been deprecated in favour of the Device Type. The new Profinet specification required that the value of these two attributes are identical.

      When building a DCP response for a Get Type Of Station DCP request, the value of abDeviceType is returned while a DCP response to Ident all is still reported with value of abTypeOfStation.

      It is expected that in any case the value of abDeviceType is returned.

      Workaround: Set field abTypeOfStation and corresponding length in Set Configuration Service to same value as abDeviceType.