Uploaded image for project: 'PROFINET IO-Device'
  1. PROFINET IO-Device
  2. PSPNS-2657

Inconcistency for DCP suboption DeviceVendor between DCP Identify Response and DCP Get Response

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V3.12.0.0
    • Fix Version/s: V3.12.2.0, V3.13.0.0
    • Component/s: Stack
    • Labels:
      None
    • Sprint:
      aktuelle Aufgaben
    • Account:
      SPC Profinet Slave (SPCPROFINE)

      Description

      DCP offers an element "DeviceVendor" with option  DevicePropertiesOption  and suboption  "SubopotionDeviceVendor". According to specification the content of this field shall be identical to DeviceType.

      In DCP Identify Response the protocol stack returns the DeviceType for this suboption. However in DCP Get Response an invalid legacy value (TypeOfStation) is used instead.

        Attachments

          Issue Links

            Expenses

              Activity

                Status Description

                  People

                  • Reporter:
                    Artem Artem R. [X] (Inactive)
                  • Votes:
                    0 Vote for this issue
                    Watchers:
                    0 Start watching this issue

                    Dates

                    • Created:
                      Updated:
                      Resolved: