Uploaded image for project: 'PROFINET IO-Device'
  1. PROFINET IO-Device
  2. PSPNS-2735

Wrong AlarmType used to report Sync mismatch and Fiber optic mismatch related diagnosis

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V3.11.0.0
    • Fix Version/s: V3.12.0.12, V3.12.2.0, V3.13.0.0
    • Component/s: None
    • Labels:
      None
    • Sprint:
      PI Sprint 2018 KW 17/18
    • Account:
      SPC Profinet Slave (SPCPROFINE)

      Description

      According to PN-Diagnosis_7142_V13_Mar17 and statemachine SYNC_DIAG)

      • the ChannelErrorType “Sync mismatch” is assigned to the AlarmType “Sync Data Changed Notification” and
      • the ChannelErrorType “Fiber optic mismatch” is assigned to the AlarmType “Port data change notification”

      Currently, the stack uses "Appears" and "Disappears" AlarmTypes to report sync and fiber optic related changes. 