unexpected LED behavior after ChannelInit while stack internal diagnosis exists

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V3.11.0.0
    • Fix Version/s: V3.12.0.1, V3.12.2.0, V3.13.0.0
    • Component/s: None
    • Labels:
      None
    • Sprint:
      PI Sprint 2017 KW 15-16
    • Account:
      SPC Profinet Slave (SPCPROFINE)

      Description

      If the protocol stack has an active internal diagnosis (e.g. wrong neighbor connected) this is indicated by SF LED static ON.

      If now a softreset is triggered (sequence RCX_CONFIG_DELETE_REQ, RCX_CHANNEL_INIT_REQ) afterwards the stack is unconfigured. However the SF LED is still on and PNS_IF_GET_DIAGNOSIS_REQ returns information that a diagnosis exists.

      It is expected that the internal diagnosis is removed in this case.