Details
Description
According to profinet specification the requested record length may exceed the max supported record size. Regardless of the request length the stack shall provide a buffer with max supported record size (e.g 32KB) to hold read response. The Application shall check the request length, if it is shorter than the real record length then an error shall be returned else the real length shall be used to generate the record response.
Attachments
Issue Links
- relates to
-
PSPNS-2610 RPC Requests occasionally not responded
- Closed
-
PSPNS-2600 Reading records causes crash of stack if the requested data length exceeds the max supported record size (Certification Issue)