CheckInd with substitute Module and substitute submodule does not work

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V3.4.38.1, V3.4.138.2
    • Fix Version/s: V3.4.48.0, V3.4.148.0
    • Component/s: None
    • Labels:
      None
    • Sprint:
      PI KW 6 2014
    • Account:
      SPC Profinet Slave (SPCPROFINE)

      Description

      if there is a difference between the expected configuration in IO-Controller and real configuration in IO-Device in the following special situation there is no data exchange possible for a submodule:
      the ModuleIdentifier differs between expected and real configuration but the SubmoduleIdentifier and IO length matches.

      In this situation the stack generates a CheckInd with "substitute Module" and "proper submodule" to application. If application sets submodule to "substitute" and returns packet to the stack this leads to a message to IO-Controller stating "substitue Module" and "wrong submodule".