Details
-
Type:
Bug
-
Status: Closed
-
Priority:
Minor
-
Resolution: Fixed
-
Affects Version/s: V3.2.0.0, V3.3.0.0, V3.4.0.0, V3.5.0.0, V3.6.0.0
-
Fix Version/s: V3.5.0.18, V3.6.0.5, V3.6.1.0 (trunk) (open)
-
Labels:None
-
Account:SPC Profinet Master V3 operational (SPCPROFINETMA)
Description
When the controller is configured to assign NameOfStation based on topology and a PA profile device is discovered by its alias name, the controller might not assign its configured NameOfStation and establish communication. The problem occurs since a PA profile device might respond DCP requestes with a different VendorId than configured in the controller. (PA devices may have have two identities)
Workaround: Set the NameOfStation with a comissioning tool or via Controllers integrated DCP request services.
Attachments
Issue Links
- is blocked by
-
PSPNCORE-909 Controller refuses to assign NameOfStation on DCP VendorID/DeviceID mismatch
-
- Closed
-