Concurrent occuring high & low prio alarms not reported to application

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Major
    • Resolution: Fixed
    • Affects Version/s: V3.1.0.0, V3.2.0.0, V3.3.0.0, V3.4.0.0, V3.5.0.0
    • Labels:
      None
    • Account:
      SPC Profinet Master (SPCPROFINETMA)

      Description

      When the Profinet IO Controller Stack receives a high and a low priority alarm for the same AR at the same time, only the last received alarm priority is reported to the application or handled internally if configured. The other alarm is never proce3ssed thus the ALPMR state machine of this priority might become stuck in state "W-User-Ack" and alarms of this priority are no more processed.