Concurrent occuring high & low prio alarms not reported to upper layers

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Major
    • Resolution: Fixed
    • Affects Version/s: V1.9.0.0, V1.10.0.0, V1.11.0.0, V1.12.0.0, V1.13.0.0, V1.14.0.0
    • Component/s: Controller
    • Labels:
      None
    • Account:
      SPC Profinet Core (SPCPROFINET)

      Description

      When the Profinet IO Controller Stack receives a high and a low priority alarm for the same AR at the same time, only the last received alarm priority is reported to the upper layers. The other alarm is never reported thus the ALPMR state machine of this priority might become stuck in state "W-User-Ack"