Receiving ApplicationReady Request prior ParameterEnd confirmationConfirm during a ParameterBegin sequence leads to AR abort

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V3.5.0.0
    • Fix Version/s: V3.5.0.1, V3.5.1.0
    • Labels:
      None
    • Account:
      SPC Profinet Master (SPCPROFINETMA)

      Description

      If the order of ApplicationReady Request and ParameterEnd Confirmation is exchanged, so that ApplicationReady is received prior to ParameterEnd Confirmation, the IO Controller abort the AR if this happens in a ParameterBegin sequence.

      If this happens during AR startup, the AR is not aborted. It is expected, that the AR is not aborted either in case of ParameterBegin sequence.