Description
While processing PrmBegin sequence, if the controller received the Application Ready request prior to the Parameter End Confirmation, the AR will be aborted with "Protocol Violation".
According to the Profinet specification, the receiving of ApplReady.req implicitly confirms the PrmEnd.req.
Attachments
Issue Links
- relates to
-
PSPNMV3-817 Receiving ApplicationReady Request prior ParameterEnd confirmationConfirm during a ParameterBegin sequence leads to AR abort