Uploaded image for project: 'PROFINET IO-Controller V3'
  1. PROFINET IO-Controller V3
  2. PSPNMV3-612

Sometimes wrong diagnosis status in Get Slave Connection Info service reported

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V3.3.0.0
    • Fix Version/s: V3.3.0.11, V3.3.1.0
    • Labels:
      None
    • Account:
      SPC Profinet Master (SPCPROFINETMA)

      Description

      In some cases an invalid diagnosis state is reported in Get Slave Connection Info service confirmation. 

      The problem occurs since the diagnosis status of a submodule is not updated for an alarm other than:

      • Alarm Type Diagnosis (0x1)
      • Alarm Type Diagnosis Disappears (0xC)
      • Alarm Type Port Data Change (0xE)

      It is expected that the diagnosis state is updated for all Diagnosis ASE attached alarm types as defined by the specification.