Submodule diagnosis status not updated properly when receiving alarm

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: None
    • Fix Version/s: V1.6.0.8, V1.10.1.0
    • Component/s: Controller
    • Labels:
      None
    • Account:
      SPC Profinet Core (SPCPROFINET)

      Description

      When the controller protocol implementation receives an alarm from a device, the internaly stored diagnosis state is not updated for alarm types other than:

      • Alarm Type Diagnosis (0x1)
      • Alarm Type Diagnosis Disappears (0xC)
      • Alarm Type Port Data Change (0xE)

      It is expected that the diagnosis state is updated for all Diagnosis ASE attached alarm types as defined by the specification.

       