Uploaded image for project: 'PROFINET Core'
  1. PROFINET Core
  2. PSPNCORE-757

SR mode with unexpected ReturnOfSubmodule alarm from the ioDevice when switching from backup to primary

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V1.15.0.0
    • Fix Version/s: V1.15.4.0, V1.16.1.0 (trunk)
    • Component/s: Device
    • Labels:
      None
    • Account:
      SPC Profinet Core (SPCPROFINET)

      Description

      The pnio device shows incorrect behavior in SR mode on the second change from backup to primary if a pull alarm was previously triggered and a plug alarm was triggered after the change. In this case, the device sends a "Return of Submodule" alarm after the change, although a PLUG alarm is expected.
      This is always the case when an AR switches from backup to primary for a second time.

      see jenkins test report

        Attachments

        1. PSPNCORE-757.patch
          2 kB
          Redouane Aamidi
        2. ReturnOfSubmodul.pcapng
          4 kB
          Norbert Kautz
        3. SR_Ownership_PSPNCORE757.pcapng
          2,94 MB
          Norbert Kautz
        4. SR_Ownership.pcapng
          2,61 MB
          Redouane Aamidi

          Expenses

            Activity

              Status Description

                People

                • Reporter:
                  NKautz Norbert Kautz
                • Votes:
                  0 Vote for this issue
                  Watchers:
                  0 Start watching this issue

                  Dates

                  • Created:
                    Updated:
                    Resolved: