Type: Bug
-
Status: Closed
-
Priority: Minor
-
Resolution: Fixed
-
Affects Version/s: V1.15.0.0
-
Fix Version/s: V1.15.4.0, V1.16.1.0 (trunk)
-
Component/s: Device
-
Labels:None
-
Account:SPC Profinet Core (SPCPROFINET)
Description
The pnio device shows incorrect behavior in SR mode on the second change from backup to primary if a pull alarm was previously triggered and a plug alarm was triggered after the change. In this case, the device sends a "Return of Submodule" alarm after the change, although a PLUG alarm is expected.
This is always the case when an AR switches from backup to primary for a second time.