Invalid topology data report for some Non-Profinet neighbour devices

    Details

    • Account:
      SPC Profinet Core (SPCPROFINET)

      Description

      For certain Non-Profinet devices the firmware reports invalid toplogy information in SNMP and record objects:

      • PDPortDataReal might contain a NameOfStation
      • lldpXPnoRemPortNoS is created from PortMacAddress if Chassis Mac Address could not be determined

      The returned information should behave as defined in specification. PDPortDataReal should contain a NameOfStation only for Profinet Devices  (Detected by existence of Profinet Chassis Id LLDP TLV) and lldpXPnoRemPortNoS  should be omitted the device is a Non-Profinet Device and the chassis mac could not be determined.