Details
Description
When the Profinet Controller Switch is used it might occur that inconsistent or old process data is sent to the devices. The problem occurs when a Provide Process Data update is requested (Handshake Cell/xChannelIOWrite/xChannelPLCActivateWrite) within the Timeintervall [35µs before the Next Cycle,Next Green Cycle Start]
It is expected that in any case consistent process data is sent to the network.
Attachments
Issue Links
- blocks
-
PSPNMV3-515 Old or inconsistent output data sent
- Closed
-
PSPNMV3-517 Update Profinet Core to V1.6.0.2
- Closed
- is blocked by
-
PSPNMV3-516 Update Profinet Core to V1.4.0.7
- Closed