Controller PPM might send inconsistent or old process data

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Major
    • Resolution: Fixed
    • Affects Version/s: V1.4.0.0 , V1.5.0.0, V1.6.0.0, V1.7.0.0
    • Component/s: None
    • Labels:
      None
    • Account:
      SPC Profinet Core (SPCPROFINET)

      Description

      When the Profinet Controller Switch is used it might occur that inconsistent or old process data is sent to the devices. The problem occurs when a Provide Process Data update is requested (Handshake Cell/xChannelIOWrite/xChannelPLCActivateWrite) within the Timeintervall [35µs before the Next Cycle,Next Green Cycle Start]

      It is expected that in any case consistent process data is sent to the network.