[Scanner] Target configuration data is restricted to 400 bytes

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V2.11.0.0
    • Fix Version/s: V2.11.0.7
    • Component/s: Firmware
    • Labels:
      None
    • Account:
      SPC EthernetIp Master (SPCETHERNETMA)

      Description

      The current implementation of the EIP Core, the size of the application segment #2 is restricted to max values of 400 bytes. Therefore the stack is unable to establish a connection and goes into a block.

      The actual limit shall be 510 bytes, which is the maximum that can be put into a single data segment when being transferred to an IO target in the ForwardOpen request.

      Documentation must be also adapted accordingly (EIP_OBJECT_REGISTER_CONNECTEION_REQ).