Details
-
Type: Bug
-
Status: Closed
-
Priority: Minor
-
Resolution: Fixed
-
Affects Version/s: V2.10.0.0
-
Fix Version/s: V2.10.0.13
-
Component/s: Firmware
-
Labels:None
-
Account:SPC EthernetIp Master (SPCETHERNETMA)
Description
The current implementation of the EIP Core, the size of the application segment #2 is restricted to max values of 400 bytes. Therefore the stack is unable to establish a connection and goes into a block.
The actual limit shall be 510 bytes, which is the maximum that can be put into a single data segment when being transferred to an IO target in the ForwardOpen request.
Documentation must be also adapted accordingly (EIP_OBJECT_REGISTER_CONNECTEION_REQ).
Attachments
Issue Links
- relates to
-
PSEIPCORE-303 [Scanner] Target configuration data is restricted to 400 bytes
- Closed
-
PSEIM-647 Update to EtherNet/IP Core V2.4.0.27