Uploaded image for project: 'PROFIBUS Slave'
  1. PROFIBUS Slave
  2. PSDPS-350

Bus ON is not set on sending a PROFIBUS_FSPMS_INIT_MS0_REQ.

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V2.6.2.0
    • Fix Version/s: V2.9.0.0
    • Component/s: Firmware
    • Labels:
      None
    • Account:
      SPC Profibus Slave (SPCPROFIBUSSL)

      Description

      Bus ON flag is not set, when PROFIBUS_FSPMS_INIT_MS0_REQ (cmd 0x0402) is sent to a not configured stack. The data sent via the request is: "01 01 00 01 01 69 0B 09 0F AF AF AF AF 9F 9F 9F 9F". In that case a confirmation PROFIBUS_FSPMS_PACKET_INIT_MS0_CNF (cmd 0x0403) without any error is received, which contains data: "6C DC 07 80 00 00 00 00 00 00 00 00". No cyclic data exchange is possible with the master device.

      PROFIBUS_FSPMS_INIT_MS0_REQ, PROFIBUS_FSPMS_INIT_MS1_REQ and PROFIBUS_FSPMS_INIT_MS2_REQ shall not be used on loadable firmware and shared memory. Those requests have to be rejected by TLR_E_UNKNOWN_COMMAND.

        Attachments

          Issue Links

            Expenses

              Activity

                Status Description

                  People

                  • Reporter:
                    DDimitrov Dimitar Dimitrov
                  • Votes:
                    0 Vote for this issue
                    Watchers:
                    0 Start watching this issue

                    Dates

                    • Created:
                      Updated:
                      Resolved: