Uploaded image for project: 'PROFINET IO Device V3 Product'
  1. PROFINET IO Device V3 Product
  2. PRODPNS-172

Feature: Add API for application to generate Alarms with specific AlarmTypes

    Details

    • Type: Requirement
    • Status: Closed
    • Priority: Minor
    • Resolution: Done
    • Affects Version/s: None
    • Fix Version/s: V3.12.0.0
    • Labels:
      None
    • Requirements Revision:
      1

      Description

      For applications implementing the PROFIenergy profile it is required to generate Alarms with AlarmType "Status". For applications implementing the PROFIsafe profile it is possible to create alarms with AlarmType "Upload and Retrieval".

      Thus such an API needs to be provided by the protocol stack to allow applications to generate specific alarms. The API service shall work the same way as current service for ProcessAlarms is used.

      The following AlarmTypes shall be supported by the new API service:

      Name                  Value
      Process		      0x0002
      Status		      0x0005
      Update		      0x0006
      Upload & Retrieval.   0x001E
      Manuf.-specif.	      0x0020-0x007F
      Profile-specif.	      0x0080-0x00FF

        Attachments

          Issue Links

            Expenses

              Activity

                Status Description

                  People

                  • Reporter:
                    BMeyer Benjamin Meyer
                  • Votes:
                    0 Vote for this issue
                    Watchers:
                    0 Start watching this issue

                    Dates

                    • Created:
                      Updated:
                      Resolved: