Details
-
Type: Bug
-
Status: Resolved
-
Priority: Minor
-
Resolution: Fixed
-
Affects Version/s: None
-
Fix Version/s: V1.0500.9.2892, V1.0600.10.58, V1.0100.9.2876
-
Component/s: EDT
-
Labels:None
-
Account:SPC Profinet Master (SPCPROFINETMA)
Description
During configuration one of the delay time caused by the cable length of a PROFINET device errors occur. The entered value is changed after saving and loading the configuration.
The error can be reproduced as follows.
- Start SYCON.net
- Insert PROFINET Controller V3 (e.g. CIFX RE/PNM V3)
- Insert PROFINET Device (e.g. CIFX RE/PNS V4.7.0.0 - V4.x SR)
- Open the PROFINET Topology Editor
- Connect a port of the controller with a port of the device
- Select the device in the topology editor
- Enter a value for the delay time in the property grid of the topology editor (see picture)
- Save configuration
- Exit SYCON.net
- Start SYCON.net
- Load configuration
- Open Topology Editor
- Select PROFINET devices
- View the delay time in the property handle
Attachments
Issue Links
- blocks
-
SYCONNET-875 Changed Delay time value in Topologie-Editor after loading configuration
- Closed