Details
-
Type: Bug
-
Status: Resolved
-
Priority: Major
-
Resolution: Fixed
-
Affects Version/s: V1.0500.191008.29314, V1.0500.191015.29406
-
Fix Version/s: V1.0500.191030.29657
-
Labels:None
-
Account:SUI Sycon (SUISYCON)
Description
When configuring a 2-axis drive with SYCON.net, a configuration error occurs.
The drive is a modular slave and the 2nd axis is configured by inserting another module into the slave configuration.
The module is inserted on slot 3.If this configuration is now loaded, the slave supplies the same values for both axes.
The slave supplies the same data for both axes because the PDO index for the 2nd module was not adapted.
This should be done via "DependOnSlot" from the ENI file.
Attachments
Issue Links
- relates to
-
DTMV1ECG-180 Misleading DependOnSlot definition in an ESI XML prevents correct configuration of PDOs
- Resolved
-
DTMV1ECM-351 Changing PDO Index or Sub Index in Generic Slave Leads to Wrong PDO List in Master Address Table
- Resolved