MST Loss counter is not allowed during hotplug. During Hotplug there is just the 130ms MST loss timer running. In HP2 with an executed S-0-0127 also the MST Loss counter was active. This is not allowed by specification.
MST Loss counter is not allowed during hotplug. During Hotplug there is just the 130ms MST loss timer running. In HP2 with an executed S-0-0127 also the MST Loss counter was active. This is not allowed by specification.