Frame configuration at Offset <8 for MDT/AT 2/3/4 impossible

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V3.1.35.0
    • Fix Version/s: V3.1.36.0
    • Component/s: None
    • Labels:
      None

      Description

      Slave reports a S-0-0127 error (S-0-1050.x.02) if tried to configure a frame offset smaller than 8 for MDT or AT 2, 3 or 4. Check is just allowed for MDT0