Uploaded image for project: 'PROFINET IO-Device V5'
  1. PROFINET IO-Device V5
  2. PSPNSV5-340

IP not set to 0.0.0.0 after receipt of of DCP ResetFactorySettings while AR is active

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V5.3.1.0
    • Fix Version/s: V5.3.2.0, V5.4.0.0
    • Labels:
      None
    • Account:
      SPC Profinet Slave (SPCPROFINE)

      Description

      When configured firrmware receives a DCP ResetFactorySettings it is expected that existing AR is aborted, NameOfStation is cleared (set to empty string) and IP address is changed to 0.0.0.0.

      However, current implementation does not reset IP to 0.0.0.0 but keeps the old one. The AR is aborted and NameOfStation correctly cleared.

        Attachments

          Issue Links

            Expenses

              Activity

                Status Description

                  People

                  • Reporter:
                    BMeyer Benjamin Meyer
                  • Votes:
                    0 Vote for this issue
                    Watchers:
                    0 Start watching this issue

                    Dates

                    • Created:
                      Updated:
                      Resolved: