Details
-
Type:
Bug
-
Status: Closed
-
Priority:
Minor
-
Resolution: Fixed
-
Affects Version/s: V5.2.1.0
-
Labels:
-
Account:SPC Profinet Slave V5 operational (SPCPROFINE)
Description
It is expected that an application receives a HIL_LINK_STATUS_CHANGE_IND message directly after it registers itself at protocol stack.
Currently this only happens if the application has configured the protocol stack upfront and a transition from "link down" to "link up" on a particular port exists.
If protocol stack is unconfigured no Link State indication will be generated at all.
Attachments
Issue Links
- blocks
-
PSPNSV5-200 Upgrade Profinet Device Interface to V1.3.0.2
-
- Closed
-
- is blocked by
-
PSPNDIF-113 Initial Link Status Change indication not sent
-
- Closed
-
- mentioned in
-
Page Loading...