Details
Description
WhIle testing IRT in large topologies instability and unexpected non-established connections can be observed, independend from the IRT configuration of SendClock and ReductionRatio.
In error case the IO Device reports an unexpected diagnosis (e.g. PTCP mismatch, PeerChassisID mismatch, ...).
Especially in networks with more than 36 netX devices the issue can be observed.
Attachments
Issue Links
- discovered by
-
PSPNS-2801 [netX51]: IRT communication may be instable or not even possible to be established in large networks
- Closed
- is cloned by
-
PSPNSV4-944 IRT communication is instable in large networks in case different cycle times are used
- Closed
- relates to
-
PSPNSV4-910 unexpected Sync offset in longer lines in case of IRT
- Closed