Details
-
Type: Bug
-
Status: Closed
-
Priority: Major
-
Resolution: Fixed
-
Affects Version/s: V4.3.1.0
-
Fix Version/s: V4.4.0.0
-
Labels:None
-
Sprint:PI Sprint 2018 KW 1-2, PI Sprint 2018 KW 3, PI Sprint 2018 KW 4
-
Account:SPC Profinet Slave (SPCPROFINE)
Description
After multiple sequences of pull and plug of network cable it may happen that no connection establishment between firmware and a Profinet IO Controller is possible.
Precondition: Acyclic ReadImplicit Service is performed in parallel to IO Device and while such request was received and not yet answered by IO Device the network cable is pulled.
Attachments
Issue Links
- relates to
-
PSPNSV4-790 Update to DCERPC V5.3.0.2
- Closed