Details

    • Account:
      SPC Profinet Slave (SPCPROFINE)

      Description

      When the protocol stack receives an alarm indication and the host application generates corresponding PNS_IF_ALARM_RES command for PNS_IF_ALARM_IND no alarm data acknowledge is sent. It is expected that an alarm data acknowledge is generated.

      This is no "real world" scenario as no known IO Controller will ever send alarms. However there exists a testcase that needs to be manually evaluated in Profinet certification tool "RT Tester".

        Attachments

          Expenses

            Activity

              Status Description

                People

                • Reporter:
                  AMesser Andreas Messer
                • Votes:
                  0 Vote for this issue
                  Watchers:
                  0 Start watching this issue

                  Dates

                  • Created:
                    Updated:
                    Resolved: