Uploaded image for project: 'PROFINET IO-Device V4'
  1. PROFINET IO-Device V4
  2. PSPNSV4-512

wrong error code used when rejecting a WriteRequest for a submodule not part of the AR

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V4.2.0.0
    • Fix Version/s: V4.2.1.0
    • Labels:
      None
    • Sprint:
      PI Sprint 2016 KW 47/48
    • Account:
      SPC Profinet Slave (SPCPROFINE)

      Description

      In case an IO Controller sends a WriteRequest for a submodule that is not part of his AR the Write is rejected. However the error code is unexpected.
      Observed errorcode: 0xDF80B208 (means "invalid subslotnumber")
      Expected errorcode: 0xDF80B600 (means "access denied")

        Attachments

          Expenses

            Activity

              Status Description

                People

                • Reporter:
                  BMeyer Benjamin Meyer
                • Votes:
                  0 Vote for this issue
                  Watchers:
                  0 Start watching this issue

                  Dates

                  • Created:
                    Updated:
                    Resolved: