Uploaded image for project: 'PROFINET IO-Device V4'
  1. PROFINET IO-Device V4
  2. PSPNSV4-511

in case Application handles I&M data the firmware shall not handle to I&M5

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Minor
    • Resolution: Fixed
    • Affects Version/s: V4.2.0.0
    • Fix Version/s: V4.2.0.17, V4.2.1.0
    • Labels:
      None
    • Sprint:
      PI Sprint 2016 KW 50/51
    • Account:
      SPC Profinet Slave (SPCPROFINE)

      Description

      If application requests to handle I&M data it is expected that I&M5 is answered with "invalid index" by the firmware. Otherwise inconsistency for applications I&M0 "IM_Supported" will occur.

      In current implementation read for I&M5 is directly answered positive by the firmware.

        Attachments

          Expenses

            Activity

              Status Description

                People

                • Reporter:
                  BMeyer Benjamin Meyer
                • Votes:
                  0 Vote for this issue
                  Watchers:
                  0 Start watching this issue

                  Dates

                  • Created:
                    Updated:
                    Resolved: