PNS_IF_CHECK_IND may report invalid ModuleState to user

    Details

    • Type: Bug
    • Status: Closed
    • Priority: Trivial
    • Resolution: Fixed
    • Affects Version/s: V4.2.0.0
    • Fix Version/s: V4.2.0.17, V4.2.1.0
    • Labels:
      None
    • Sprint:
      PI Sprint 2016 KW 47/48
    • Account:
      SPC Profinet Slave (SPCPROFINE)

      Description

      In case a module has one submodule plugged and a second submodule requested by IO Controller the firmware generates a PNS_IF_CHECK_IND for this second submodule.
      However the ModuleState reported to the user is invalid.
      Firmware reports "No Module" although obviously a module is plugged in the specific slot.